Troubleshooting 8-37
When STATUS lamp is flashing in amber
Description
On-screen
message
Recommended action
HDD 0 Fault An error was detected in hard disk drive in slot 0.
HDD 1 Fault An error was detected in hard disk drive in slot 1.
HDD 2 Fault An error was detected in hard disk drive in slot 2.
HDD 3 Fault An error was detected in hard disk drive in slot 3.
Check installation status of failed hard disk drive.
If the same error persists, contact your service representative.
E-Keying Error In the Blade Enclosure, combination of installation locations of CPU blade,
mezzanine card, and switch module is not correct. Thus, an unconformity of
interface signal was detected and the CPU blade failed to power on.
Refer to the User’s Guide of the Blade Enclosure to make sure that the they
are installed in correct locations.
Replace the CPU blade.
If the same error persists, contact your service representative.
Location Error
In the Blade Enclosure, the installation location of CPU blade is incorrect, or
the installation locations of the fan and CPU blade are incorrect. Thus, the
CPU blade failed to power on.
1. Refer to the User’s Guide of the Blade Enclosure to make sure that the
CPU blade is installed in correct locations.
2. Check if the fans and CPU blades are installed in correct locations.
Replace the CPU blade.
If the same error persists, contact your service representative.
Cooling Error In the Blade Enclosure, the number of fans installed is insufficient or the
installed fan is faulty. Thus, the CPU blade failed to power on due to
insufficient cooling power.
AmbientTempAlm07 A high temperature warning occurred in CPU unit.
AmbientTempAlm00 A low temperature warning occurred in CPU unit.
1. Check if fans in Blade Enclosure work normally.
2. Refer to the User’s Guide of the Blade Enclosure to make sure that the
sufficient number of fans are installed in correct locations.
3. Check if the fans and CPU blades are installed in correct locations.
4. Check installation status of heat sink of the CPU blade.
5. Check if the ambient temperature of installation location satisfies the
operation guarantee condition.
Replace the CPU blade.
If the same error persists, contact your service representative.