
Installing Server 3-3
Space 40 cm or more on top, 1 m or more
on the front and rear, and 60 cm or more on
the right and left.
Room that can maintain the following
conditions:
[When operating]
Temperature: 10 to 35ºC*
Humidity: 20 to 80%
Temperature gradient: ±10ºC/hr
Atmospheric pressure: 749 to 1040hpa
[When not operating]
Temperature: 5 to 40ºC*
Humidity: 10 to 80%
Temperature gradient: ±15ºC/hr
Atmospheric pressure: 749 to 1040hpa
Level and reinforced floor.
200 VAC outlets. These outlets should
be located within the range to which the
power cords can reach. (The server can
operate in the 200 VAC environment.)
100 VAC outlets with parallel two-pole
earth (The server can operate in the 200
VAC environment. These outlets are
required when your operating
environment includes one or more
optional device operating at 100 VAC.
* It is recommended that the server should be used in a room where
temperature is in the range between 15 to 25℃.
WARNING
Observe the following precautions to use the server safely. There is a risk of a
death or serious injury. For details, see “Notes for Safe Handling” in Chapter 1.
Do not install the equipment in non-designated places.
Do not connect the ground wire to a gas pipe.
Comentarios a estos manuales